The State of Delaware New Regulations Management System is coming soon in 2024 More Info

Delaware.gov logo

Authenticated PDF Version

DEPARTMENT OF natural resources and environmental control

Division of Air and Waste Management

Statutory Authority: 7 Delaware Code, Chapter 60, (7 Del.C. Ch. 60)
7 DE Admin. Code 1142

PROPOSED

REGISTER NOTICE

1. Title of the Regulation:

Repromulgation and revision of 7 DE Admin. Code 1142 Section 2: Control of NOx Emissions from Industrial Boilers and Process Heaters at Petroleum Refineries and submittal of the re-promulgated regulation to the US Environmental Protection Agency (EPA) as a revision to Delaware State Implementation Plan (SIP).

2. Brief Synopsis of the Subject, Substance and Issues:

The Clean Air Act Amendments of 1990 (CAA) requires Delaware, as part of the Philadelphia-Wilmington-Atlantic City non-attainment area, to attain the 8-hour ozone National Ambient Air Quality Standard (NAAQS) of 0.08 ppm by 2010. Since nitrogen oxides (NOx) are a major precursor to the formation of ozone in the lower atmosphere, Delaware must reduce NOx emissions in order to reduce ambient ozone concentrations, and thus attain the NAAQS. As a part of the overall effort towards attainment, in July 2007, the Delaware Department of Natural Resources and Environmental Control (DNREC) promulgated 7 DE Admin. Code 1142 Section 2, which required large industrial boilers and process heaters with heat input capacities equal to or greater than 200 million British thermal units per hour (mmBTU/hour) at Delaware petroleum refineries to meet certain NOx emission limits.

DNREC is proposing to repromulgate the regulation and revise the emission limits for 3 boilers in the Premcor Refinery at Delaware City and to submit the regulation to EPA as a revision to Delaware’s SIP. DNREC believes that the new limits are adequate for achieving necessary and timely NOx emission reductions from the subject sources. The revisions are being proposed pursuant to a settlement of an appeal to the Environmental Appeals Board by the Premcor Refinery on 7 DE Admin. Code 1142 Section 2 as promulgated in July 2007.

3. Possible Terms of the Agency Action:

None.

4. Statutory Basis or Legal Authority to Act:

7 Del.C., Chapter 60, Environmental Control

5. Other Regulations That May Be Affected By The Proposal:

None

6. Notice of Public Comment:

A public hearing will be held on September 30, 2009, beginning at 6:00 pm, in DNREC Conference Room A, 391 Lukens Drive, New Castle, DE 19720.

7. Prepared By:

Frank F. Gao Phone: (302) 323-4542 Date: August 7, 2009

E-Mail: Frank.Gao@state.de.us

1142 Specific Emission Control Requirements

 
12/12/2001
1.0 Control of NOx Emissions from Industrial Boilers

1.1 Purpose

New Castle County and Kent County are part of the Philadelphia-Wilmington-Trenton 1-hour ozone non-attainment area. All areas of Delaware impact this non-attainment area. On December 19, 1999, the EPA identified an emission reduction “shortfall” associated with this non-attainment area. Promulgation of 1.0 of this regulation is one measure that the Department is taking to mitigate this shortfall.

In determining the applicability of 1.0 of this regulation, the Department attempted to minimize the impact on facilities that recently installed NOx controls under 7 DE Admin. Code 1112 (NOx RACT) and 7 DE Admin. Code 1137/1139 (NOx Budget Trading Program). The Department did this by regulating only large sources that, as of the effective date of 1.0 of this regulation, emitted NOX at a rate greater than the rate identified in Table I 3-1 of 7 DE Admin. Code 1112, were not equipped with NOx emission control technology, and were not subject to the requirements of 7 DE Admin. Code 1139. In effect, 1.0 of this regulation regulates sources that remain high NOx emitters after the application of RACT and post RACT requirements, and that have not committed substantial capital funds to reduce NOx emissions.

1.2 Applicability

1.2.1 The provisions of 1.0 of this regulation apply to any person that owns or operates any combustion unit with a maximum heat input capacity of equal to or greater than 100 million BTU per hour, except that 1.0 of this regulation shall not apply to any unit that, as of the effective date of 1.0 of this regulation:

1.2.1.1 Emits NOx at a rate equal to or less than the rate identified in Table 3-1 of DE Admin. Code 1112.

1.2.1.2 Is equipped with low NOx burner, flue gas recirculation, selective catalytic reduction, or selective non-catalytic reduction technology.

1.2.1.3 Is subject to the requirements of 7 DE Admin. Code 1139.

1.2.2 The requirements of 1.0 of this regulation are in addition to all other state and federal requirements.

1.2.3 Affected persons shall comply with the requirements of 1.3 of this regulation as soon as practicable, but no later than May 1, 2004.

1.3 Standards.

1.3.1 The NOx emission rate from any unit subject to 1.0 of this regulation shall be equal to or less than the following:

1.3.1.1 Between May 1st through September 30th of each year, inclusive: 0.10 lb/mmBTU, 24-hour calendar day average.

1.3.1.2 During all times that gaseous fuel is being fired: 0.10 lb/mmBTU, 24-hour calendar day average.

1.3.1.3 During all times not covered by 1.3.1.1 and 1.3.1.2 of this regulation: 0.25 lb/mmBTU, 24-hour calendar day average.

1.3.2 As an alternative to compliance with the requirements of 1.3.1 of this regulation, compliance may be achieved through the procurement and retirement of NOx allowances authorized for use under 7 DE Admin. Code 1139, as follows:

1.3.2.1 The actual 24-hour calendar day average NOx emission rate in pounds per million BTU shall be determined for each day of unit operation, using CEMs operated in accordance with 1.4 of this regulation.

1.3.2.2 The actual heat input to each unit in million but shall be determined for each day of unit operation, using methods proposed by the person subject to 1.0 of this regulation and acceptable to the Department.

1.3.2.3 0.10 or 0.25, as applicable and consistent with 1.3.1 of this regulation, shall be subtracted from the rate determined in 1.3.2.1 of this regulation.

1.3.2.4 To obtain the number of pounds of NOx emitted for a particular day, the emission rate determined in 1.3.2.3 of this regulation shall be multiplied by the heat input to the unit for that day determined in 1.3.2.2 of this regulation. If the emission rate determined in 1.3.2.3 of this regulation is equal to or less than zero, then the number of pounds of NOx emitted for that day shall be zero.

1.3.2.5 Not later than the 20th day of each month:

1.3.2.5.1 The number of pounds of NOx emissions calculated pursuant to 1.3.2.4 of this regulation shall be summed for each calendar month, the result shall be divided by 2000, and shall be rounded to the nearest whole ton.

1.3.2.5.2 For each ton of NOx emissions calculated pursuant to 1.3.2.5.1 of this regulation, records shall be maintained demonstrating that one NOx allowance owned by the person subject to 1.0 of this regulation is identified and available, by serial number, for retirement.

1.3.2.6 Not later than February 1 of each calendar year, the NOx allowances identified pursuant to 1.3.2.5.2 of this regulation for the previous calendar year, shall be submitted to the Department for retirement. Such submission shall detail the calculations specified in 1.3.2.1 through 1.3.2.5 of this regulation, and shall indicate the serial number of each allowance to be retired.

1.4 Monitoring Requirements. Compliance with the NOx emission standards specified in 1.0 of this regulation shall be determined based on CEM data collected in accordance with the requirements of 3.1.2 of 7 DE Admin. Code 1117 (Performance Specification 2), and in compliance with the requirements of 40 CFR, Part 60, Appendix F.

1.5 Recordkeeping and Reporting Requirements.

1.5.1 Not later than 180 days after the effective date of 1.0 of this regulation, any person subject to 1.0 of this regulation shall develop, and submit to the Department for approval, a schedule for bringing the affected emission unit or units into compliance with the requirements of 1.0 of this regulation. Such schedule shall include, at a minimum, all of the following:

1.5.1.1 The method by which compliance will be achieved

1.5.1.2 The dates by which the affected person commits to completing the following major increments of progress, as applicable:

1.5.1.2.1 Completion of engineering;

1.5.1.2.2 Submission of permit applications;

1.5.1.2.3 Awarding of contracts for construction or installation;

1.5.1.2.4 Initiation of construction;

1.5.1.2.5 Completion of construction;

1.5.1.2.6 Commencement of trial operation;

1.5.1.2.7 Initial compliance testing;

1.5.1.2.8 Submission of compliance testing reports;

1.5.1.2.9 Commencement of normal operations (in full compliance).

1.5.2 Any person subject to 1.0 of this regulation shall submit to the Department an initial compliance certification not later than May 1, 2004. The initial compliance certification shall, at a minimum, include the following information:

1.5.2.1 The name and the location of the facility.

1.5.2.2 The address and telephone number of the person responsible for the facility.

1.5.2.3 Identification of the subject source or sources.

1.5.2.4 The applicable standard.

1.5.2.5 The method of compliance.

1.5.2.6 Certification that each subject source is in compliance with the applicable standard

1.5.2.7 All records necessary for determining compliance with the standards of 1.0 of this regulation shall be maintained at the facility for a period of five years.

1.5.3 Any person subject to 1.0 of this regulation shall, for each occurrence of excess emissions, within 30 calendar days of becoming aware of such occurrence, supply the Department with the following information:

1.5.3.1 The name and location of the facility.

1.5.3.2 The subject source or sources that caused the excess emissions.

1.5.3.3 The time and date of first observation of the excess emissions.

1.5.3.4 The cause and expected duration of the excess emissions.

1.5.3.5 The estimated rate of emissions (expressed in the units of the applicable emission limitation) and the operating data and calculations used in determining the magnitude of the excess emissions.

1.5.3.6 The proposed corrective actions and schedule to correct the conditions causing the excess emissions.

1.5.4 Any person subject to 1.0 of this regulation shall maintain all information necessary to demonstrate compliance with the requirements of 1.0 of this regulation for a minimum period of five years. Such information shall be immediately made available to the Department upon verbal and written request.

07/11/2007 xx/xx/2009

2.0 Control of NOx Emissions from Industrial Boilers and Process Heaters at Petroleum Refineries

2.1 Purpose

2.1.1 The purpose of Section 2.0 of this regulation is to reduce NOX emissions from Delaware's large industrial boilers and process heaters that are located at petroleum refineries.

2.1.2 Under the 8-hour ozone national ambient air quality standard (NAAQS), the state of Delaware is part of the Philadelphia-Wilmington-Atlantic City, PA-DE-MD-NJ moderate non-attainment area (NAA). The entire NAA, including Delaware, is required by the Clean Air Act (CAA) to attain the 8-hour ozone NAAQS by 2010. After attainment, the area must maintain compliance with the NAAQS. By implementing Section 2.0 of this regulation, NOx emission reductions from the affected boilers and heaters shall contribute to (1) attainment and maintenance of the 8-hour ozone standard, and (2) improvement of the ambient air quality, in both Delaware and the entire NAA.

2.1.3 Additionally, New Castle County of Delaware is a part of the Philadelphia-Wilmington-Camden, PA-DE-NJ NAA for the annual fine particulate matter (PM2.5) NAAQS, and is required by the CAA to attain the NAAQS by 2010. Since NOx is a significant precursor to PM2.5 formation, reducing NOx emissions will also assist in attainment and maintenance of the PM2.5 standard.

2.2 Applicability and Compliance Dates

2.2.1 Section 2.0 of this regulation applies to any industrial boiler or process heater with a maximum heat input capacity of equal to or greater than 200 million BTUs per hour (mmBTU/Hour) (except for any Fluid Catalytic Cracking Unit carbon monoxide (CO) boiler), which is operated or permitted to operate within a petroleum refinery facility on the effective date of this section. This comprises the following nine (9) units at the Delaware City refinery:

2.2.1.1 Crude Unit Vacuum Heater (Unit 21-H-2);

2.2.1.2 Crude Unit Atmospheric Heater (Unit 21-H-701);

2.2.1.3 Fluid Coking Unit Carbon Monoxide boiler (Unit 22-H-3);

2.2.1.4 Steam Methane Reformer Heater (Unit 37-H-1);

2.2.1.5 Continuous Catalyst Regenerator Reformer Heater (Unit 42-H-1,2,3);

2.2.1.6 Boiler 1 (Unit 80-1);

2.2.1.7 Boiler 2 (Unit 80-2);

2.2.1.8 Boiler 3 (Unit 80-3);

2.2.1.9 Boiler 4 (Unit 80-4).

2.2.2 The requirements of Section 2.0 of this regulation are in addition to all other state and federal requirements.

2.2.3 The following units shall be in compliance with the requirements of Section 2.0 of this regulation on and after July 11, 2007: Crude Unit Atmospheric Heater (Unit 21-H-701), Steam Methane Reformer Heater (Unit 37-H-1) and Boiler 2 (Unit 80-2).

2.2.4 The following units shall be in compliance with the requirements of Section 2.0 of this regulation as soon as practicable, but not later than:

2.2.4.1 December 31, 2008: Boiler 1 (Unit 80-1) and Crude Unit vacuum Heater (Unit 21-H-2).

2.2.4.2 May 1, 2011: Boiler 3 (Unit 80-3) and Boiler 4 (Unit 80-4).

2.2.4.3 December 31, 2012: Continuous Catalyst Regenerator Reformer Heater (Unit 42-H-1, 2, 3).

2.3 Standards.

The owner or operator of any industrial boiler or process heater identified in Section 2.2.1 of this regulation shall not allow NOx to be emitted at a rate that exceeds the following meet the applicable NOx emission limitation identified in the following sections:

2.3.1 For the Fluid Coking Unit Carbon Monoxide boiler (Unit 22-H-3), Reserved.

2.3.2 For the Steam Methane Reformer (SMR) Heater (Unit 37-H-1), Reserved.

2.3.3 For Boiler 1 (Unit 80-1), Boiler 3 (Unit 80-3) and Boiler 4 (Unit 80-4), shall not operate after May 1, 2011. On or before May 1, 2011 the owner or operator of Boiler 3 and Boiler 4 shall request that any operating permit issued by the Department be cancelled. 0.015 lb/mmBTU, on a 24-hour rolling average basis.

2.3.4 For any unit not covered by 2.3.1, 2.3.2, or 2.3.3, 0.04 lb/mmBTU, on a 24-hour rolling average basis.

2.3.5 The standards set out in 2.3 of this regulation shall not apply to the start-up and shutdown of equipment when emissions from such equipment during a start-up and shutdown are addressed in an operation permit issued pursuant to the provisions of §2 of Regulation 1102.

2.4 Monitoring Requirements. Compliance with the NOx emission standards specified in 2.3.1, 2.3.2, and 2.3.4 of this regulation shall be determined based on CEM data collected in accordance with the appropriate requirements set forth in 40 CFR, Part 60, Appendix B, Performance Specification 2, and the QA/QC requirements in 40 CFR Part 60, Appendix F.

2.5 Recordkeeping and Reporting Requirements

2.5.1 Not later than 180 days after the effective date of Section 2.0 of this regulation, any person subject to Section 2.0 of this regulation shall develop, and submit to the Department, a schedule for bringing the affected emission unit(s), identified in Section 2.2.4, into compliance with the requirements of Section 2.3 of this regulation. Such schedule shall include, at a minimum, all of the following:

2.5.1.1 The method by which compliance will be achieved.

2.5.1.2 The dates by which the affected person plans to complete the following major increments of progress, as applicable:

2.5.1.2.1 Completion of engineering;

2.5.1.2.2 Submission of permit applications;

2.5.1.2.3 Awarding of contracts for construction and/or installation;

2.5.1.2.4 Initiation of construction;

2.5.1.2.5 Completion of construction;

2.5.1.2.6 Commencement of trial operation;

2.5.1.2.7 Initial compliance testing;

2.5.1.2.8 Submission of compliance testing reports;

2.5.1.2.9 Commencement of normal operations (in full compliance).

2.5.2 Any person subject to Section 2.0 of this regulation shall submit to the Department an initial compliance certification by September 10, 2007 for units identified in Section 2.2.3 of this regulation and, for units identified in Section 2.2.4, by the compliance date specified in Section 2.2.4. The initial compliance certification shall include, at a minimum, all of the following information:

2.5.2.1 The name and the location of the facility;

2.5.2.2 The name, address and telephone number of the person responsible for the facility;

2.5.2.3 Identification of the subject source(s);

2.5.2.4 The applicable standard;

2.5.2.5 The method of compliance;

2.5.2.6 Certification that each subject source is in compliance with the applicable standard.

2.5.3 Any person subject to Section 2.0 of this regulation shall, for each occurrence of excess emissions above the standards of Section 2.3 of this regulation, within thirty (30) calendar days of becoming aware of such occurrence, supply the Department with the following information:

2.5.3.1 The name and location of the facility;

2.5.3.2 The subject source(s) that caused the excess emissions;

2.5.3.3 The time and date of first observation of the excess emissions;

2.5.3.4 The cause and expected duration of the excess emissions;

2.5.3.5 The estimated rate of emissions (expressed in the units of the applicable emission limitation) and the operating data and calculations used in determining the magnitude of the excess emissions;

2.5.3.6 The proposed corrective actions and schedule to correct the conditions causing the excess emissions.

2.5.4 Any person subject to Section 2.0 of this regulation shall maintain all information necessary to determine and demonstrate compliance with the requirements of this section for a minimum period of five (5) years. Such information shall be immediately made available to the Department upon verbal and written request.

5 DE Reg. 1299 (12/01/01)
11 DE Reg. 75 (07/01/07)
12 DE Reg. 347 (09/01/08)
13 DE Reg. 382 (09/01/09) (Prop.)
+