Title 1 Authorites, Boards and Commissions
700 Delaware State Fire Prevention Commission
700 Delaware State Fire Prevention Regulations
Appendices
Appendix A
This Appendix is not part of the requirements of this Regulation, but is included for informational purposes only.
The material contained in Appendix A of the Delaware State Fire Prevention Regulations is interspersed among the verbiage of Parts 701 through Part 706 of this Regulation and, therefore, Appendix A is not repeated here. Appendix A material is shown as a “Note” directly after the paragraph in which it addresses.
Appendix B
Delaware Statutes Governing State Fire Prevention Commission and State Fire Marshall
Title 16 Health and Safety:
Chapter 64: http://delcode.delaware.gov/title16/c064/index.shtmlAmusement Rides Safety Inspection and Insurance Act
Chapter 66 Fire Prevention:
http://delcode.delaware.gov/title16/c066/sc01/index.shtmlSubchapter I. State Fire Marshall and State Fire Prevention Commission
http://delcode.delaware.gov/title16/c066/sc02/index.shtmlSubchapter II. Smoke Detectors
http://delcode.delaware.gov/title16/c066/sc03/index.shtmlSubchapter III. False Fire Alarms
Chapter 88: http://delcode.delaware.gov/title16/c088/index.shtmlStudent Dormitories and Student Residential Housing Fire Suppression System
Appendix C
Cross Reference of Statutes Applicable to Fire Regulations
Delaware Code cross reference for those sections applicable to the Delaware State Fire Regulations.
Title 7 Conservation:
Chapter 7, Section 713: http://delcode.delaware.gov/title7/c007/sc01/index.shtml#713Fire regulations; penalty.
Title 11 Crimes and Criminal Procedure:
Chapter 5 Specific Offenses:
Subchapter I Inchoate Crimes
Section 501 http://delcode.delaware.gov/title11/c005/sc01/index.shtml#501Criminal solicitation in the third degree; class A misdemeanor
Section 502 http://delcode.delaware.gov/title11/c005/sc01/index.shtml#502Criminal solicitation in the second degree; class F felony
Section 503 http://delcode.delaware.gov/title11/c005/sc01/index.shtml#503Criminal solicitation in the first degree; class E felony
Section 511 http://delcode.delaware.gov/title11/c005/sc01/index.shtml#511Conspiracy in the third degree; class A misdemeanor.
Section 512 http://delcode.delaware.gov/title11/c005/sc01/index.shtml#512Conspiracy in the second degree; class G felony.
Section 513 http://delcode.delaware.gov/title11/c005/sc01/index.shtml#513Conspiracy in the first degree; class E felony.
Section 531 http://delcode.delaware.gov/title11/c005/sc01/index.shtml#531Attempt to commit a crime.
Subchapter II Offenses Against the Person
Subpart A. Assaults and Related Offenses
Section 603 http://delcode.delaware.gov/title11/c005/sc02/index.shtml#603Reckless endangering in the second degree; class A misdemeanor
Section 604 http://delcode.delaware.gov/title11/c005/sc02/index.shtml#604Reckless endangering in the first degree; class E felony.
Section 621 http://delcode.delaware.gov/title11/c005/sc02/index.shtml#621Terroristic threatening.
Subchapter III Offenses Involving Property
Subpart A. Arson and Related Offenses
Section 801 http://delcode.delaware.gov/title11/c005/sc03/index.shtml#801Arson in the third degree; affirmative defense; class G felony.
Section 802 http://delcode.delaware.gov/title11/c005/sc03/index.shtml#802Arson in the second degree; affirmative defense; class D felony.
Section 803 http://delcode.delaware.gov/title11/c005/sc03/index.shtml#803Arson in the first degree; class C felony.
Section 804 http://delcode.delaware.gov/title11/c005/sc03/index.shtml#804Reckless burning or exploding; class A misdemeanor
Section 805 http://delcode.delaware.gov/title11/c005/sc03/index.shtml#805Cross or religious symbol burning; class A misdemeanor
Section 843 http://delcode.delaware.gov/title11/c005/sc03/index.shtml#843Theft; false pretense.
Section 846 http://delcode.delaware.gov/title11/c005/sc03/index.shtml#846Extortion; class E felony.
Section 871 http://delcode.delaware.gov/title11/c005/sc03/index.shtml#871Falsifying business records; class A misdemeanor.
Section 913 http://delcode.delaware.gov/title11/c005/sc03/index.shtml#913Insurance fraud; class G felony.
Subchapter VI Offenses Against Public Administration
Subpart A. Bribery and Improper Influence
Section 1243 http://delcode.delaware.gov/title11/c005/sc06/index.shtml#1243Obstructing fire-fighting operations; class A misdemeanor
Section 1244 http://delcode.delaware.gov/title11/c005/sc06/index.shtml#1244Hindering prosecution; class A misdemeanor
Section 1245 http://delcode.delaware.gov/title11/c005/sc06/index.shtml#1245Falsely reporting an incident; class A misdemeanor.
Subchapter VII Offenses Against Public Health, Order and Decency
Subpart A. Riot, Disorderly Conduct and Related Offenses
Section 1323 http://delcode.delaware.gov/title11/c005/sc07/index.shtml#1323Obstructing public passages; violation
Section 1338http://delcode.delaware.gov/title11/c005/sc07/index.shtml#1338Bombs, incendiary devices, Molotov cocktails and explosive devices; class D felony.
Title 16 Health and Safety:
Chapter 64 Chapter 64 http://delcode.delaware.gov/title16/c064/index.shtml Amusement Rides Safety Inspection and Insurance Act:
Chapter 65, Section 6501:
http://delcode.delaware.gov/title16/c065/index.shtmlLiability for negligent burning.
Chapter 66 Fire Prevention
Subchapter I: http://delcode.delaware.gov/title16/c066/sc01/index.shtmlState Fire Marshal and State Fire Prevention Commission
Subchapter II: http://delcode.delaware.gov/title16/c066/sc02/index.shtmlSmoke Detectors
Subchapter III: http://delcode.delaware.gov/title16/c066/sc03/index.shtmlFalse Fire Alarms
Chapter 69 Fireworks
Section 6901 http://delcode.delaware.gov/title16/c069/index.shtml#6901Selling or possessing fireworks; exceptions.
Section 6902 http://delcode.delaware.gov/title16/c069/index.shtml#6902Discharging rifle or other explosives; exceptions.
Section 6903 http://delcode.delaware.gov/title16/c069/index.shtml#6903Permit for public display of fireworks; actions by injured persons.
Section 6904 http://delcode.delaware.gov/title16/c069/index.shtml#6904Confiscation of illegally stored fireworks or explosives.
Chapter 70 Storage of Explosives
Section 7001 http://delcode.delaware.gov/title16/c070/index.shtml#7001Signs on premises containing stored explosives.
Section 7002 http://delcode.delaware.gov/title16/c070/index.shtml#7002Exceptions.
Section 7003 http://delcode.delaware.gov/title16/c070/index.shtml#7003Penalties
Chapter 71 Sale, Purchase, Receipt, Possession, Transportation, Use, Safety and Control of Explosive Materials
Section 7101 http://delcode.delaware.gov/title16/c071/index.shtml#7101Scope
Section 7102 http://delcode.delaware.gov/title16/c071/index.shtml#7102Definitions
Section 7103 http://delcode.delaware.gov/title16/c071/index.shtml#7103General Provisions
Section 7104 http://delcode.delaware.gov/title16/c071/index.shtml#7104Purchase, receipt and possession
Section 7105 http://delcode.delaware.gov/title16/c071/index.shtml#7105Sale
Section 7106 http://delcode.delaware.gov/title16/c071/index.shtml#7106Licensed blasters
Section 7107 http://delcode.delaware.gov/title16/c071/index.shtml#7107Administration
Section 7108 http://delcode.delaware.gov/title16/c071/index.shtml#7108Authority to purchase in contiguous states
Section 7109 http://delcode.delaware.gov/title16/c071/index.shtml#7109Records
Section 7110 http://delcode.delaware.gov/title16/c071/index.shtml#7110Safety
Section 7111 http://delcode.delaware.gov/title16/c071/index.shtml#7111Notice to affected persons
Section 7112 http://delcode.delaware.gov/title16/c071/index.shtml#7112Transportation
Chapter 73 http://delcode.delaware.gov/title16/c073/index.shtmlProducts Utilizing Petroleum Derivatives
Chapter 75 http://delcode.delaware.gov/title16/c075/index.shtmlFire Excapes and Exits
Chapter 88 http://delcode.delaware.gov/title16/c088/index.shtmlStudent Dormitories and Student Residential Housing Fire Suppression Systems
Title 21
Chapter 70 http://delcode.delaware.gov/title21/c070/index.shtmlFire Lanes
Title 29
Chapter 82 Sections 8223-8230 of this title shall be known and may be cited as the "Hazardous Materials Transportation Act of 1979."
Section 8222 http://delcode.delaware.gov/title29/c082/index.shtml#8222Short Title
Section 8223 http://delcode.delaware.gov/title29/c082/index.shtml#8223Declaration of policy; findings of fact
Section 8224 http://delcode.delaware.gov/title29/c082/index.shtml#8224Definitions
Section 8225 http://delcode.delaware.gov/title29/c082/index.shtml#8225Adoption of federal requirements
Section 8226 http://delcode.delaware.gov/title29/c082/index.shtml#8226State Emergency Response Commission
Section 8227 http://delcode.delaware.gov/title29/c082/index.shtml#8227Remedies
Section 8228 http://delcode.delaware.gov/title29/c082/index.shtml#8228Jurisdiction; penalties
Section 8229 http://delcode.delaware.gov/title29/c082/index.shtml#8229Exclusive state regulation; general repealer
Appendix D
NFPA Publications For Guidance
Numerical Listing
The following Standards, Recommendations, Recommended Practices, Manuals, Guides, and Model Laws are included here for reference and guidance in the application of the State of Delaware Fire Prevention Rules and Regulations when a particular problem is not otherwise covered by a Code, Standard, or Law Provision. The Fire Marshal may use the provisions of these Standards, Recommendations, Recommended Practices, Manuals, Guides, and Model Laws as appropriate criteria for meeting the intent of the State of Delaware Fire Prevention Rules and Regulations in those cases.
NFPA NO. |
DATE OF PUBLI-CATION |
TITLE |
11C |
1995 |
Mobile Foam Apparatus, Standard for |
43D |
1994 |
Code for the Storage of Pesticides |
461 |
1996 |
Recommended Safe Practice for Storage of Forest Products |
49 |
1994 |
Hazardous Chemicals Data |
531 |
2004 |
Guide on Fire Hazards in Oxygen Enriched Atmospheres |
681 |
2002 |
Guide for Venting of Deflagrations |
70B1 |
2006 |
Recommended Practice for Electrical Equipment Maintenance |
70E1 |
2004 |
Standard for Electrical Safety Requirements for Employee Workplaces |
771 |
2000 |
Recommended Practice on Static Electricity |
80A1 |
2001 |
Recommended Practice for Protection of Buildings from Exterior Fire Exposures |
851 |
2004 |
Boiler and Combustion Systems Hazards Code |
97 |
1996 |
Standard Glossary of Terms Relating to Chimneys, Vents, and Heat-Producing Appliances |
99B1 |
2005 |
Standard for Hypobaric Facilities |
101A1 |
2004 |
Guide on Alternative Approaches to Life Safety |
1051 |
2003 |
Standard for the Installation of Smoke Door Assemblies |
1151 |
2003 |
Standard for Laser Fire Protection |
1301 |
2003 |
Standard for Fixed Guideway Transit Systems |
203 |
1995 |
Guide for Roof Coverings and Roof Deck Construction |
2041 |
2002 |
Standard for Smoke and Heat Venting |
231E1 |
1996 |
Recommended Practice for the Storage of Baled Cotton |
2321 |
2000 |
Standard for Protection of Records |
2511 |
2006 |
Standard Methods of Tests of Fire Resistance of Building Construction and Materials |
2521 |
2003 |
Standard Methods of Fire Tests of Door Assemblies |
2531 |
2006 |
Standard Method of Test for Critical Radiant Flux of Floor Covering Systems Using a Radiant Heat Energy Source |
2551 |
2006 |
Standard Method of Test of Surface Burning Characteristics of Building Materials |
2561 |
2003 |
Standard Methods of Fire Tests of Roof Coverings |
2571 |
2000 |
Standard on Fire Test for Window and Glass Block Assemblies |
258 |
2001 |
Standard Research Test Method for Determining Smoke Generation of Solid Materials |
2591 |
2003 |
Standard Test Method for Potential Heat of Building Materials |
2601 |
2003 |
Standard Methods of Tests and Classification System for Cigarette Ignition Resistance of Components of Upholstered Furniture |
2611 |
2003 |
Standard Method of Test for Determining Resistance of Mock-Up Upholstered Furniture Material Assemblies to Ignition by Smoldering Cigarettes |
2621 |
2002 |
Standard Method of Test for Flame Travel and Smoke of Wires and Cables for Use in Air-Handling Spaces |
263 |
1994 |
Heat and Visible Smoke Release Rates for Materials and Products, Standard Method of Test for |
264 |
1995 |
Standard Method of Test of Heat and Visible Smoke Release Rates for Materials and Products Using an Oxygen Consumption Calorimeter |
264A |
1994 |
Method of Test for Heat Release Rates for Upholstered Furniture Components or Composites and Mattresses Using an Oxygen Consumption Calorimeter |
2651 |
2002 |
Standard Methods of Fire Tests for Evaluating Room Fire Growth Contribution of Textile Coverings on Full Height Panels and Walls |
2681 |
2001 |
Standard Test Method for Determining Ignitibility of Exterior Wall Assemblies Using a Radiant Heat Energy Source |
2691 |
2000 |
Standard Test Method for Developing Toxic Potency Data for Use in Fire Hazard Modeling |
2911 |
2002 |
Recommended Practice for Fire Flow Testing and Marking of Hydrants |
295 |
1991 |
Standard for Wild Fire Control |
297 |
1995 |
Guide on Principles and Practices for Communications Systems |
299 |
1991 |
Standard for Protection of Life and Property from Wildfire |
3181 |
2006 |
Standard for the Protection of Semiconductor Fabrication Facilities |
325 |
1994 |
Guide to Fire Hazard Properties of Flammable Liquids, Gases, and Volatile Solids |
328 |
1992 |
Recommended Practice for the Control of Flammable and Combustible Liquids and Gases in Manholes, Sewers, and Similar Underground Structures |
3291 |
2005 |
Recommended Practice for Handling Releases of Flammable and Combustible Liquids and Gases |
419 |
1992 |
Guide for Master Planning Airport Water Supply Systems for Fire Protection |
4231 |
2004 |
Standard for Construction and Protection of Aircraft Engine Test |
4241 |
2004 |
Guide for Airport/Community Emergency Planning |
491M |
1991 |
Manual of Hazardous Chemical Reactions |
4971 |
2004 |
Recommended Practice for the Classification of Flammable Liquids, Gases, or Vapors and of Hazardous (Classified) Locations for Electrical Installations in Chemical Process Areas |
497M |
1991 |
Manual for Classification of Gases, Vapors, and Dusts for Electrical Equipment in Hazardous (Classified) Locations |
4991 |
2004 |
Recommended Practice for the Classification of Combustible Dusts and of Hazardous (Classified) Locations for Electrical Installations in Chemical Process Areas |
512 |
1994 |
Standard for Truck Fire Protection |
5551 |
2004 |
Guide on Methods for Evaluating Potential for Room Flashover |
6001 |
2005 |
Standard on Industrial Fire Brigades |
6011 |
2005 |
Standard for Security Service in Fire |
7011 |
2004 |
Standard Methods of Fire Tests for Flame Propagation of Textiles and Films |
7051 |
2003 |
Recommended Practice for a Field Flame Test for Textiles and Films |
8011 |
2003 |
Standard for Facilities Handling Radioactive Materials |
802 |
1993 |
Recommended Practice for Fire Protection for Nuclear Research and Production Reactors |
803 |
1993 |
Standard for Fire Protection for Light Water Nuclear Power Plants |
8041 |
2006 |
Standard for Fire Protection for Advanced Light Water Reactor Electric Generating Plants |
8051 |
2006 |
Performance-Based Standard for Fire Protection for Light Water Reactor Electric Generating Plants |
8201 |
2003 |
Standard for Fire Protection in Wastewater Treatment and Collection Facilities |
8501 |
2005 |
Recommended Practice for Fire Protection for Electric Generating Plants and High Voltage Direct Current Converter Stations |
8511 |
2005 |
Recommended Practice for Fire Protection for Hydroelectric Generating Plants |
9011 |
2006 |
Standard Classifications for Incident Reporting and Fire Protection Data |
9141 |
2001 |
Code for Fire Protection of Historic Structures |
1141 |
2003 |
Standard for Fire Protection in Planned Building Groups |
16001 |
2004 |
Standard on Disaster/Emergency Management and Business Continuity Programs |
APPENDIX D
NFPA Publications For Guidance
Alphabetical Listing
The following Standards, Recommendations, Recommended Practices, Manuals, Guides and Model Laws are included here for reference and guidance in the application of the State of Delaware Fire Prevention Rules and Regulations when a particular problem is not otherwise covered by a Code, Standard, or Law Provision. The Fire Marshal may use the provisions of these Standards, Recommendations, Recommended Practices, Manuals, Guides and Model Laws as appropriate criteria for meeting the intent of the State of Delaware Fire Prevention Rules and Regulations in those cases.
NFPA NO. |
DATE OF PUBLI-CATION |
TITLE |
4231 |
2004 |
Aircraft Engine Test, Standard for Construction and Protection of |
4241 |
2004 |
Airport/Community Emergency Planning, Guide for |
419 |
1992 |
Airport Water Supply Systems for Fire Protection, Guide for Master Planning |
101A1 |
2004 |
Alternative Approaches to Life Safety, Guide on |
231E |
1996 |
Baled Cotton, Recommended Practice for the Storage of |
851 |
2004 |
Boiler and Combustion Systems Hazards Code |
2511 |
2006 |
Building Construction and Materials, Standard Methods of Tests of Fire Resistance of |
2591 |
2003 |
Building Materials, Standard Test Method for Potential Heat of |
2551 |
2006 |
Building Materials, Standard Method of Test of Surface Burning Characteristics of |
491M |
1991 |
Chemical Reactions, Hazardous, Manual of |
49 |
1994 |
Chemicals Data, Hazardous |
97 |
1996 |
Chimneys, Vents, and Heat-Producing Appliances, Standard Glossary of Terms Relating to |
2601 |
2003 |
Cigarette Ignition Resistance of Components of Furniture, Standard Methods of Tests and Classification System for |
297 |
1995 |
Communications Systems, Guide on Principals and Practices for |
16001 |
2004 |
Standard on Disaster/Emergency Management and Business Continuity Programs |
2521 |
2003 |
Door Assemblies, Standard Methods of Fire Tests of |
497M |
1991 |
Electrical Equipment in Hazardous (Classified) Locations, Manual for Classification of Gases, Vapors, and Dusts for |
70B |
2006 |
Electrical Equipment Maintenance, Recommended Practice for |
8501 |
2005 |
Electric Generating Plants and High Voltage Direct Current Converter Stations, Recommended Practice for Fire Protection for |
8041 |
2006 |
Electric Generating Plants, Standard for Fire Protection for Advanced Light Water Reactor |
8051 |
2006 |
Reactor Electric Generating Plants, Performance-Based Standard for Fire Protection for Light Water |
4971 |
2004 |
Electrical Installations in Chemical Process Areas, Recommended Practice for the Classification of Flammable Liquids, Gases, or Vapors and of Hazardous (Classified) Locations for |
4991 |
2004 |
Recommended Practice for the Classification of Combustible Dusts and of Hazardous (Classified) Locations for Electrical Installations in Chemical Process Areas |
70E1 |
2004 |
Electrical Safety Requirements for Employee Workplaces, Standard for |
80A1 |
2001 |
Exterior Fire Exposures, Recommended Practice for Protection of Buildings from |
2681 |
2001 |
Exterior Wall Assemblies, Standard Test Method for Determining Ignitibility of, Using a Radiant Heat Energy Source |
7051 |
2003 |
Field Flame Test for Textiles and Films, Recommended Practice for a |
2691 |
2000 |
Fire Hazard Modeling, Standard Test Method for Developing Toxic Potency Data for Use in |
3291 |
2005 |
Flammable and Combustible Liquids and Gases, Recommended Practice for Handling Releases of |
328 |
1992 |
Flammable and Combustible Liquids and Gases in Manholes, Sewers, and Similar Underground Structures, Recommended Practice for the Control of |
325 |
1994 |
Flammable Liquids, Gases, Volatile Solids, Guide to Fire Hazard Properties of |
5551 |
2004 |
Flashover, Room, Guide on Methods for Evaluating Potential for |
2531 |
2006 |
Floor Covering Systems Using a Radiant Heat Energy Source, Standard Method of Test for Critical Radiant Flux of |
46 |
1996 |
Forest Products, Recommended Safe Practice for Storage of |
263 |
1994 |
Heat and Visible Smoke Release Rates for Materials and Products, Standard Method of Test for |
264 |
1995 |
Heat and Visible Smoke Release Rates for Materials and Products Using an Oxygen Consumption Calorimeter, Standard Method of Test for |
9141 |
2001 |
Historic Structures, Code for Fire Protection of |
2911 |
2002 |
Hydrants, Recommended Practice for Fire Flow Testing and Marking of |
8511 |
2005 |
Hydroelectric Generating Plants, Recommended Practice for Fire Protection for |
99B1 |
2005 |
Hypobaric Facilities, Standard for |
9011 |
2006 |
Incident Reporting and Fire Protection Data, Standard Classifications for |
2611 |
2003 |
Ignition by Smoldering Cigarettes, Standard Method of Test for Determining Resistance of Mock-Up Upholstered Furniture Material Assemblies to |
6001 |
2005 |
Industrial Fire Brigades, Standard on |
1151 |
2003 |
Laser Fire Protection, Standard for |
11C |
1995 |
Mobile Foam Apparatus, Standard for |
803 |
1993 |
Nuclear Power Plants, Light Water, Standard for Fire Protection for |
802 |
1993 |
Nuclear Research and Production Reactors, Recommended Practice |
531 |
2004 |
Oxygen Enriched Atmospheres, Guide on Fire Hazards in |
43D |
1994 |
Pesticides, Code for the Storage of |
11411 |
2003 |
Planned Building Groups, Standard for Fire Protection in |
8011 |
2003 |
Radioactive Materials, Standard for Facilities Handling |
2321 |
2000 |
Standard for Protection of Records |
203 |
1995 |
Roof Coverings and Roof Deck Construction, Guide on |
2561 |
2003 |
Roof Coverings, Standard Methods of Fire Tests of |
6011 |
2005 |
Security Service in Fire Loss Prevention, Standard for |
3181 |
2006 |
Semiconductor Fabrication Facilities, Standard for the Protection of |
1051 |
2003 |
Smoke Door Assemblies, Standard for the Installation of |
2041 |
2002 |
Smoke and Heat Venting, Standard for |
2581 |
2001 |
Smoke Generation of Solid Materials, Standard Research Test for Determining |
771 |
2003 |
Static Electricity, Recommended Practice on |
2651 |
2002 |
Standard Methods of Fire Tests for Evaluating Room Fire Growth Contribution of Textile Coverings on Full Height Panels and Walls |
7011 |
2004 |
Textiles and Films, Standard Methods of Fire Tests for Flame Propagation of |
1301 |
2003 |
Transit Systems, Fixed Guideway, Standard for |
512 |
1994 |
Truck Fire Protection, Standard for |
264A |
1994 |
Upholstered Furniture Components or Composites and Mattresses Heat Release Rates for |
681 |
2002 |
Venting of Deflagrations, Guide for |
8201 |
2003 |
Wastewater Treatment and Collection Facilities, Standard for Fire Protection in |
295 |
1991 |
Wild Fire Control, Standard for |
299 |
1991 |
Wildfire, Standard for Protection of Life and Property from |
2621 |
2002 |
Wires and Cables for Use in Air-Handling Spaces, Standard Method of Test for Flame Travel and Smoke of |
2571 |
2000 |
Window and Glass Block Assemblies, Standard on Fire Test for |
Appendix E
Permits, Licenses, and Other Fees
Amusement Ride Fees. The cost of any fee for amusement rides shall be $20.00 per year, not to exceed a total of $100.00. (16 Del. C. §6403)
Blaster’s License. The cost of a Blaster’s License shall be $10.00 per year. (16 Del. C. §7107(b)).
Certificate Of Inspection For Fire Alarm Signaling Systems Fees. The cost of an Annual Certificate of Inspection shall be as follows:
(a) Apartment or other multi-family dwellings:
(1) Five (5) or less buildings per complex: $25.00 for each fire alarm system;
The term "complex" as is referenced in these portions of the Delaware State Fire Prevention Regulation, is to indicate apartments or multi-family buildings that are located in the same general geographic area and owned by the same individual(s) or management group or other business entity. |
(2) More than five (5) buildings per complex: $15.00 for each fire alarm system up to a maximum of twenty (20) buildings. Maximum fee per complex not to exceed $300.00 for fire alarm systems.
(b) All other occupancies - $25.00 per system
(16 Del. C. §6607(g)(5)c.).
Certificate Of Inspection For Fire Suppression Systems Fees. The cost of an Annual Certificate of Inspection shall be as follows:
(a) Apartment or other multi-family dwellings:
(1) Five (5) or less buildings per complex: $25.00 for each fire suppression system;
The term "complex" as is referenced in these portions of the Delaware State Fire Prevention Regulation, is to indicate apartments or multi-family buildings that are located in the same general geographic area and owned by the same individual(s) or management group or other business entity. |
(2) More than five (5) buildings per complex: $15.00 for each fire suppression system up to a maximum of twenty (20) buildings. Maximum fee per complex not to exceed $300.00 for fire suppression systems.
(b) All other occupancies - $25.00 per system
(16 Del. C. §6607(g)(5)c.).
Explosives Storage. The cost of a license to store explosives shall be $10.00 per year. (16 Del. C. §7101(b)).
Fire Alarm Central Station, Remote Station, or Monitoring Service or Company License. The cost of an annual license for a Fire Alarm Central Station, Remote Station, or Monitoring Service or Company shall be $25.00.
Fire Alarm Signaling System Company License. The cost of an annual license for a Fire Alarm Signaling System Company shall be $25.00.
Fire Alarm Signaling System Certificate Holder. The cost of an annual certificate for a CERTIFICATE HOLDER of a Fire Alarm Signaling System Company shall be $25.00.
Fire Suppression System Company License. The cost of an annual license for a Fire Suppression System Company shall be $25.00.
Fire Suppression System Certificate Holder. The cost of an annual certificate for a CERTIFICATE HOLDER of a Fire Suppression System Company shall be $25.00.
In-House License Fees. Where a Fire Alarm Signaling System In-House or Fire Suppression System In-House License is issued, a maximum of $100.00 per Fire Alarm Signaling or Fire Suppression System shall be charged for each system serviced by the system owner16 Del. C. §6607 (g)(5)a.)
Licenses/Permits That Require An On-Site Inspection Prior To Issuing A License Or Permit. $25.00 per license or permit. (16 Del. C. §6607(g)(5)c.).
Licenses/Permits That Do Not Require An On-Site Inspection Prior To Issuing A License Or Permit. $10.00 per license or permit. (16 Del. C. §6607(g)(5)c.).
License To Service Portable Fire Extinguishers. The cost of a License to service portable fire extinguishers shall be $50.00 per year 16 Del. C. §6607(g)(5)b.).
Plan Review User Fee Schedule. The State Fire Marshal, under the provisions 16 Del. C. §6607(g)(1) - §6607(g)(4), hereby establishes the below listed Plan Review User Fee to be paid by the submitter of plans to the State of Delaware, Office of State Fire Marshal.
(a) Effective July 1, 2009: .007/.003
7/10 of 1% of construction costs up to the first million dollars of construction costs.
3/10 of 1% of construction costs in excess of one million dollars of construction costs.
Minimum Plan Review Fee of $150.00 on all plans.
(b) Sub-Division Plan Reviews
1. Major Subdivisions - $150.00
2. Minor Subdivisions - $150.00
(c) Special Fees For Warehouses
When calculating the fee schedule for warehouses and similar low use buildings, the submitter shall have the choice of using the fee schedule listed in A and B above or, he may use the following calculation:
Gross Square Footage X $30 = Construction Cost
Then apply the percentages listed in A and B above to this calculated construction cost.
(d) Revision Of Fees.
The fees as authorized by 16 Del.C. §6607 shall be the maximum allowed by the State Fire Prevention Commission, and shall be reviewed every two years.
Detailed Fee List
Annual Certificate/License Required
Annual Certificate/License |
Annual Fee |
Covered Malls |
$ 25.00 |
Explosives |
$ 10.00 |
Fire Alarm Central Station, Remote Station, or Monitoring Service or Company License |
$ 25.00 |
Fire Alarm Certificate Holder |
$ 25.00 |
Fire Alarm Certificate of Inspection per System |
$ 25.00 |
Exception: Apartment or other multi-family dwellings: 1) Five (5) or less buildings per complex: $25.00 for each fire alarm system;
The term “complex” as is referenced in these portions of the Delaware State Fire Prevention Regulation, is to indicate apartments or multi-family buildings that are located in the same general geographic area and owned by the same individual(s) or management group or other business entity. 2) More than five (5) buildings per complex: $15.00 for each fire alarm system up to a maximum of twenty (20) buildings. Maximum fee per complex not to exceed $300.00 for fire alarm systems. | |
Fire Alarm Company License |
$ 25.00 |
Fire Extinguisher License |
$ 50.00 |
Fire Suppression Certificate Holder |
$ 25.00 |
Fire Suppression Certificate of Inspection per System |
$ 25.00 |
Exception: Apartment or other multi-family dwellings: 1) Five (5) or less buildings per complex: $25.00 for each fire suppression system; The term “complex” as is referenced in these portions of the Delaware State Fire Prevention Regulation, is to indicate apartments or multi-family buildings that are located in the same general geographic area and owned by the same individual(s) or management group or other business entity. 2) More than five (5) buildings per complex: $15.00 for each fire suppression system up to a maximum of twenty (20) buildings. Maximum fee per complex not to exceed $300.00 for fire suppression systems. | |
Fire Suppression Company License |
$ 25.00 |
Fireworks Shooters |
$ 25.00 |
Flammable/Comustible Liquids |
$ 25.00 |
Fun House |
$ 25.00 |
In-House Fire Alarm Signaling System License (per system) |
$ 100.00 |
In-House Fire Suppression System License (per system) |
$ 100.00 |
Liquified Petroleum Gas |
$ 25.00 |
Places of Assembly |
$ 25.00 |
Public Accomodations |
$ 25.00 |
Permit Required For Single Event | |
Single Event |
Event Fee |
Amusement Rides (Not to exceed $100.00) |
$ 20.00 per ride |
Amusement Attraction |
$ 25.00 |
Bowling Lanes |
$ 25.00 |
Burning |
$ 25.00 |
Exhibits, Craft, Trade Shows |
$ 25.00 |
Explosives |
$ 25.00 |
Fireworks |
$ 25.00 |
Impairment of Fire Protection |
$ 25.00 |
Place of Assembly Special Events |
$ 25.00 |
Appendix F
Table One
Owner Performed Testing, Inspection, and Maintenance of Fire Suppression Systems As Required by Regulation 703, Chapter 1 and the Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems NFPA 25, 2008 Edition
This brief summary of periodic tests, inspections, and maintenance is not all inclusive, and, to assist in the performance of these services, the user is advised to purchase the applicable documents from NFPA (1-800-344-3555). These periodic tests, inspections, and maintenance may be performed by the owner or the owner's maintenance staff. A log book must be maintained by the owner for each system. The log book must include the date the service was performed, the type of service performed, and the person performing the service. An asterisk (*) denotes servicing which must be performed at least annually (once a year) by a company licensed by the Office of State Fire Marshal, Licensing Division, (302) 739-4394.
Item |
Activity |
Frequency |
Service |
Section # |
General |
||||
Gauges, Pressure |
Inspection |
*Monthly |
Wet System |
§5.2.4.1 |
*Weekly |
Dry, Preaction, Deluge Systems |
§5.2.4.2 | ||
Control Valves |
Inspection |
*Weekly |
Valves (not supervised or secured) |
§12.3.2.1 |
*Monthly |
supervised and secured Valves |
§12.3.2.1.1 | ||
Testing |
*Annual |
Operated though its full range |
§12.3.3.1 | |
Alarm Devices |
Testing |
*Semiannual |
Vane type devices |
§5.3.3. |
Testing |
*Quarterly |
Wet System: flow thru inspectors test |
§5.3.3.3 | |
Dry/Preaction/Deluge: use bypass |
§5.3.3.5 | |||
Fire Dept Conn |
Inspection |
*Quarterly |
Visible, accessible, operating condition |
§12.7 |
Alarm Valves |
Inspection |
*Monthly |
Free of damage, leakage, in proper position |
§12.4.1.1 |
Backflow Prevention Assemblies | ||||
Reduced Pressure |
Inspection |
*Weekly |
Differential sensing valve relief port |
§12.6.1.2 |
R.P. Detector |
Inspection |
*Weekly |
Differential sensing valve relief port |
§12.6.1.2 |
Main Drain |
Testing |
*Quarterly |
Test to check condition of water supply |
§12.6.1 |
Water Flow Alarm |
Testing |
*Quarterly |
Test in accordance with manufacturer |
§12.2.7 |
Preaction/Deluge Valves |
||||
Enclosure |
Inspection |
Daily |
In cold weather only, maintain 40 degrees |
§12.4.3.1 |
Valve Exterior |
Inspection |
*Monthly |
Free of damage, leakage, trim valves set properly, electrical components operational |
12.4.3.1.6 |
Dry Valves/Quick-Opening Devices |
||||
Enclosure |
Inspection |
Daily |
In cold weather only, maintain 40 degrees |
§12.4.4.1.1 |
Valve Exterior |
Inspection |
*Monthly |
Free of damage, leakage, trim valves set properly, electrical components operational |
§12.4.4.1.3 |
Pressure Regulating and Relief Valves |
||||
Sprinkler System |
Inspection |
*Quarterly |
Valves open, no leakage, proper pressure |
§12.5.1.1 |
Hose Connection |
Inspection |
*Quarterly |
Valves okay, no leakage, all parts present |
§12.5.2.1 |
Hose Rack |
Inspection |
*Quarterly |
Valves okay, no leakage |
§12.5.3.1 |
Fire Pump Relief Valves |
||||
Circulation |
Inspection |
*Weekly |
Water flows thru valve at churn |
§12.5.6.1 |
Pressure |
Inspection |
*Weekly |
Water flows thru valve at rated pressure |
§12.5.6.2 |
Standpipes |
||||
Piping |
Inspection |
*Quarterly |
All parts present, operable, in good condition |
§6.2.1 |
Inspection |
Monthly |
See Table 6.1 |
§6.2.1 | |
Hose Valve |
Inspection |
*Quarterly |
All parts present & in good condition |
§6.2.1 |
Outlets |
Inspection |
Monthly |
See Table 6.1 |
§6.2.1 |
Fire Pumps |
||||
Pump House |
Inspection |
*Weekly |
In cold weather, see Tables 8.1 |
§8.1 |
System |
Inspection |
*Weekly |
See Table 8.5.3 |
§8.2 |
Pump Operation |
||||
No Flow |
Testing |
*Weekly |
Electric: auto start and run 10 minutes min |
§8.3.2.1 |
Diesel: auto start and run 30 minutes min |
§8.3.2.1 | |||
Foam Water Sprinkler System | ||||
Discharge Devices |
Inspection |
*Monthly |
No damage/corrosion, in place w/proper aim |
§11.2.5 |
Strainer |
Inspection |
*Quarterly |
Blow-down Valve, blankets/screens |
§11.2.9.2 |
Drainage |
Inspection |
*Quarterly |
Free of blockage, embankments good repair |
§11.2.8 |
Fittings/Piping |
Inspection |
*Quarterly |
No damage/corrosion/missing parts |
§11.2.3 |
Hangers/Support |
Inspection |
*Quarterly |
No damage/corrosion, attachments secure |
§11.2.4 |
Foam Water Sprinkler Proportioning System |
||||
Standard Pressure |
Inspection |
*Monthly |
No corrosion, ball drip valves free/opened |
§11.2.9.5.1 |
Bladder Tank |
Inspection |
*Monthly |
No corrosion, water control valves in position |
§11.2.9.5.2 |
Line Proportioner |
Inspection |
*Monthly |
No corrosion, pressure vacuum vent operable |
§11.2.9.5.3 |
Standard Balanced |
Inspection |
*Monthly |
Pressure vacuum vent, sensing lines, gauges |
§11.2.9.4 |
In-Line Balanced |
Inspection |
*Monthly |
Pressure vacuum vent, sensing lines, gauges |
§11.2.9.5.5 |
Orifice Plate |
Inspection |
*Monthly |
Pressure vacuum vent, sensing lines, gauges |
§11.2.9.5.6 |
Private Fire Service Mains |
||||
Hose House |
Inspection |
Quarterly |
Accessible, free of damage, all parts present |
§7.2.2.7 |
Maintenance |
Annually |
Hoses and all parts in usable condition |
§7.4.5 | |
Hydrant House |
Inspection |
Quarterly |
Accessible, free of damage, all parts present |
§7.2.2.7 |
Maintenance |
Annually |
Hoses and all parts in usable condition |
§7.4.5 | |
Hydrant: Wall/Dry |
Inspection |
Annually |
Accessible, no water in barrel, operable |
§7.2.2.4 |
Testing |
Annually |
Flow Test, minimum one minute |
§7.3.2 | |
Maintenance |
Annually |
Lubricate stems, caps, plugs, threads |
§7.4.3.1 | |
Hydrant: Wet |
Inspection |
Annually |
Accessible, free of damage, operable |
§7.2.2.5 |
Testing |
Annually |
Flow Test, minimum one minute |
§7.3.2 | |
Maintenance |
Annually |
Lubricate stems, caps, plugs, threads |
§7.4.3.1 | |
Monitor Nozzle |
Inspection |
2 Times/Year |
Free of damage, no leakage, no corrosion |
§7.2.2.6 |
Testing |
Annually |
Full range oscillation and movement |
§7.3.3 | |
Testing |
Annually |
When attached to hydrants, per NFPA 25 |
§7.3.3.1 | |
Maintenance |
Annually |
Lubricate |
§7.4.4 | |
Mainline Strainer |
Inspection |
Annually |
Clean, free of damage and corrosion |
§7.2.2.3 |
Maintenance |
Annually |
Clean annually & after each use |
§7.4.2 | |
Piping: |
||||
Exposed |
Inspection |
Annually |
Free of damage, no leakage, no corrosion |
§7.2.2.1 |
Testing |
Every 5 Years |
Fire Flow Test for internal conditions |
§7.3.1 | |
Underground |
Testing |
Every 5 Years |
Fire Flow Test for internal conditions |
§7.3.1 |
Water Spray Fixed System |
||||
Drainage |
Inspection |
Monthly |
Free of blockage, embankments good repair |
§10.2.8 |
Fittings/Piping |
Inspection |
*Quarterly |
No damage/corrosion/rust/missing parts |
§10.2.4 |
Hangers/Support |
Inspection |
*Quarterly |
No damage/corrosion/rust/missing parts |
§10.2.4 |
Heat/Valve Room |
Inspection |
*Monthly |
Maintain 40 degrees F |
§10.2.1.5 |
Inspection |
Weekly |
In cold weather, inspect daily |
§10.2.1.5 | |
Nozzles |
Inspection |
*Monthly |
No damage/corrosion, in place w/proper aim |
§10.2.1 |
Strainers |
Inspection |
*Per Mfr |
Flushed clear after each operation or test |
§10.2.7 |
Water Storage Tanks |
||||
Condition/Level |
Inspection |
Monthly |
In cold weather only |
§9.2.1 |
Level |
Maintenance |
Monthly |
regardless if water level alarm is provided |
§9.3 |
Level Alarm |
Testing |
*2 Times/Year |
High and Low water level alarms tested |
§9.3.5 |
Heating System |
Inspection |
Daily |
In cold weather only |
§9.2.6.6 |
Temperature |
Inspection |
Daily |
Only in cold weather, maintain 40 deg. F |
§9.2.3.2 |
Low Alarm |
Testing |
*Monthly |
Where provided, test in cold weather |
§9.3.3 |
High Alarm |
Testing |
Monthl y |
In cold weather, test limit switches |
§9.3.4 |
Air Pressure |
Inspection |
*Monthly |
In pressure tanks |
§9.2.2.2 |
Tank Exterior |
Inspection |
*Quarterly |
Free of damage, no leakage, sound structure |
§9.2.5.1 |
Tank Area/Yard |
Inspection |
Quarterly |
Free of combustibles, corrosion, erosion, ice |
§9.2.5.2 |
Hoops/Grillage |
Inspection |
Annually |
In wooden tanks, no damage/deterioration |
§9.2.5.4 |
Tank Surface |
Inspection |
Annually |
Paint/Coat/Insulation no damage/deterioration |
§9.2.5.5 |
Maintenance |
Per Mfr |
Repaint steel tanks per manufacturer |
§9.4.4 | |
Tank Support |
Maintenance |
*Per Mfr |
Embankment Supported Rubberized Fabric |
§9.4.6 |
Expansion Joints |
Inspection |
*Annually |
Where provided, no leaks, no cracks |
§9.2.5 |
Sediment |
Maintenance |
*2 Times/Year |
Drain and/or flush tank |
§9.4.5 |
Inspection: A visual examination to verify an item is in operating condition and free of physical damage.
Testing: A procedure used to determine the status of a system operating as intended by conducting physical checks.
Maintenance: Work performed to keep equipment operable or to make repairs.
*Servicing may be performed by an owner, but must be performed at least annually by a licensed company.
Appendix F
Table Two
Licensed Company Required
Testing, Inspection, and Maintenance of Fire Suppression Systems As Required by Part III, Chapter 1 and the Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems NFPA 25, 2002 Edition
This brief summary of periodic tests, inspections, and maintenance is not all inclusive, and, to assist in the performance of these services, the user is advised to purchase the applicable documents from NFPA (1-800-344-3555). These periodic services must be performed by a company licensed by the Office of State Fire Marshal, Licensing Division, (302) 739-4394. A log book must be maintained by the licensed company for each system. The log book must include the date the service was performed, the type of service performed, and the person performing the service. An asterisk (*) denotes servicing which may be performed by an owner, but must be performed at least annually (once a year) by a licensed company. A licensed company must forward a Certificate of Inspection to the Office of State Fire Marshal within 30 days of the annual inspection.
Item |
Activity |
Frequency |
Service |
Section # |
General |
||||
Gauges, Pressure |
Inspection |
*Monthly |
Wet System |
§5.2.4.1 |
*Weekly |
Dry, Preaction, Deluge Systems |
§5.2.4.2 | ||
Testing |
Every 5 Years |
Calibration Test |
§5.3.2 | |
Control Valves |
Inspection |
*Weekly |
Valves (not supervised or secured) |
§12.3.2.1 |
*Monthly |
Supervised/Secured Valves & Tamper Sws |
§12.3.2.1 | ||
Testing |
Annually |
Operate Valve - full range of motion |
§12.3.3 | |
Maintenance |
Annually |
Oil/grease valve stems, open & close |
§12.4.1.3 | |
Alarm Devices |
Inspection |
*Quarterly |
Free of damage/all connections secure |
§5.3.3.2 |
Testing |
*Quarterly |
Wet System: flow thru inspectors test |
§5.3.3.3 | |
Dry/Preaction/Deluge: use bypass |
§5.3.3.5 | |||
Hangars |
Inspection |
Annually |
Inspect for damaged or loose hangars |
§5.2.3 |
Piping |
Inspection |
Annually |
No damage, leakage, corrosion, etc. |
§5.2.2 |
Sprinklers/Standard |
Inspection |
Annually |
No corrosion, obstructions, paint, etc |
§5.2.1.1 |
Testing |
After 50 Years |
Submit samples to lab for test |
§5.3.1.1.1.1 | |
Testing |
+10 Years |
Repeat Every 10 years thereafter |
||
Fast Response |
Testing |
After 20 Years |
Submit samples to lab for test |
§5.3.1.1.1.2 |
+10 Years |
Repeat Every 10 years thereafter |
|||
High Temp |
Testing |
After 5 Years |
Submit samples to lab for test |
§5.3.1.1.1.3 |
FD Connection |
Inspection |
*Quarterly |
Visible, accessible, operating condition |
§12.7. |
Alarm Valves |
Inspection |
*Monthly |
Free of damage, leakage, in proper position |
§12.4.1.1 |
Inspection |
Every 5 Years |
Internal inspection |
§12.4.1.2 | |
Check Valves |
Inspection |
Every 5 Years |
Internal inspection |
§12.4.2.1 |
Backflow Prevention Assemblies | ||||
Reduced Pressure |
Inspection |
*Weekly |
Differential sensing valve relief port |
§12.6.1.2 |
R.P. Detector |
Inspection |
*Weekly |
Differential sensing valve relief port |
§12.6.1.2 |
Entire Assembly |
Testing |
Annually |
Test in accordance with AHJ procedures |
§12.6.2, |
Main Drain |
Testing |
*Quarterly |
Test to check condition of water supply |
§12.2.6 |
Water Flow Alarm |
Testing |
*Quarterly |
Test in accordance with manufacturer |
§12.2.7 |
Preaction/Deluge Valves |
||||
Valve Exterior |
Inspection |
*Monthly |
No damage, trim valves set properly, etc |
§12.4.1.3.6 |
Valve Interior |
Inspection |
Annually |
Internal inspection |
§12.4.1.3.7 |
Strainers/Filters |
Inspection |
Every 5 Years |
Internal inspection |
§12.4.3.1.8 |
Priming Water |
Testing |
Quarterly |
Test levels per manufacturer’s instructions |
§12.4.3.2.1 |
Low Press Alarm |
Testing |
Quarterly |
Test per manufacturer’s instructions |
§12.4.3.2.10 |
Full Flow Test |
Testing |
Annually |
In warm weather, test per manufacturer |
§12.4.3.2.2 |
Valves |
Testing |
Annually |
During Full Flow Test, clean & repair interior |
§12.4.3.3.2 |
Dry Valves/Quick-Opening Devices (Q.O.D.) |
||||
Valve Exterior |
Inspection |
*Monthly |
No damage, trim valves set properly, etc |
§12.4.4.1.4 |
Valve Interior |
Inspection |
Annually |
Internal inspection |
§12.4.4.1.5 |
Strainers/Filters |
Inspection |
Every 5 Years |
Internal Inspection |
§12.4.4.1.6 |
Priming Water |
Testing |
Quarterly |
Test levels per manufacturer’s instructions |
§12.4.4.2.1 |
Low Air Alarm |
Testing |
Quarterly |
Test per manufacturer’s instructions |
§12.4.4.2.6 |
Q.O.D. |
Testing |
Quarterly |
Test per manufacturer’s instructions |
§12.4.4.2.4 |
Maintenance |
Annually |
During Trip Test, clean & repair interior |
§12.4.4.3.2 | |
Trip Test |
Testing |
Annually |
In warm weather, test w/valve partially open |
§12.4.4.2.2 |
Full Flow Test |
Testing |
Every 3 Years |
In warm weather, test w/valve fully open |
§12.4.4.2.2.2 |
Pressure Regulating and Relief Valves |
||||
Sprinkler System |
Inspection |
*Quarterly |
Valves open, no leakage, proper pressure |
§12.5.1.1 |
Testing |
Annually |
Flow test on each valve |
§12.5.1.2 | |
Hose Connection |
Inspection |
*Quarterly |
Valves okay, no leakage, all parts present |
§12.5.2.1 |
Hose Rack |
Inspection |
*Quarterly |
Valves okay, no leakage |
§12.5.3.1 |
Fire Pump Relief Valves |
||||
Circulation |
Inspection |
*Weekly |
Water flows thru valve at churn |
§12.5.6.1 |
Pressure |
Inspection |
*Weekly |
Water flows thru valve at rated pressure |
§12.5.6.2 |
Circulation |
Testing |
Annually |
Valve closes per manufacturer's listing |
§12.5.6.1.2 |
Pressure Relief |
Testing |
Annually |
Valve adjusted during Annual Fire Pump Test |
§12.5.6.2.2 |
Hose Connections |
Testing |
Every 5 Years |
Full Flow Test per manufacturer |
§12.5.2.2 |
Hose Rack |
Testing |
Every 5 Years |
Full Flow Test per manufacturer |
§12.5.3.2 |
Obstruction |
Maintenance |
Every 5 Years |
Investigate to ensure piping is free of debris |
Table 5.1 |
Anti-Freeze |
Testing |
Annually |
Measure specific gravity of solution |
§5.3.4 |
Standpipes |
||||
Hose Valve Outlet |
Inspection |
*Quarterly |
All parts present & in good condition |
§6.2.1 |
Piping |
Inspection |
*Quarterly |
All parts present, operable, in good condition |
§6.2.1 |
Cabinet |
Inspection |
Annually |
All parts present, operable, in good condition |
§6.2.1 |
Hose |
Inspection |
Annually |
All parts present, operable, in good condition |
§6.2.1 |
Testing |
Every 5 Years |
Per NFPA 1962 |
§6.3 | |
Testing |
Every 3 Years |
Per NFPA 1962 |
§6.3 | |
Hose Storage |
Inspection |
Annually |
All parts present, operable, in good condition |
§6.2.1 |
Testing |
Annually |
Test for smooth operation |
§6.3 | |
Hose Nozzle |
Testing |
Annually |
Test for smooth operation |
§6.3 |
Hydrostatic |
Testing |
Every 5 Years |
200 psi for 2 hours |
§6.3 |
Water Supply |
Testing |
Every 5 Years |
Flow designed volume, pressure @ remote |
§6.3.1.1 |
Fire Pumps |
||||
Pump House |
Inspection |
*Weekly |
In cold weather, see Tables 8.1 & 8.5.3 |
§8.2.2 |
System |
Inspection |
*Weekly |
See Table 8.5.3 |
§8.2.2 |
Pump Operation |
||||
No Flow |
Testing |
*Weekly |
Electric: auto start & run 10 minutes min |
§8.3.1.2 |
Diesel: auto start and run 30 minutes min |
§8.3.1.3 | |||
Flow |
Testing |
Annually |
Annual Flow Test |
§8.3.3 |
Hydraulics, Transmission Electrical, Controller, Motor, and Diesel Parts |
Maintenance |
Annually |
Establish preventive maintenance program, per manufacturer’s instructions, on all components of the pump assembly |
§8.5.3 |
Foam Water Sprinkler System |
||||
Discharge Devices |
Inspection |
*Monthly |
No damage/corrosion, in place w/proper aim |
§11.2.5 |
Strainer |
Testing |
Annually |
Discharge patterns/proper location/position |
§11.3.3.6 |
Inspection |
*Quarterly |
Blow-down Valve, blankets/screens |
§11.2.7 | |
Testing |
Annually |
After each test/remove/clean baskets/screens |
§11.2.7.2 | |
Maintenance |
Annually |
Inspect and clean after each test |
§11.4 | |
Drainage |
Inspection |
*Quarterly |
Free of blockage, embankments good repair |
§11.2.9 |
Fittings/Piping |
Inspection |
*Quarterly |
No damage/corrosion/missing parts |
§11.2.3 |
Hangers/Support |
Inspection |
*Quarterly |
No damage/corrosion, attachments secure |
§11.-2.4 |
Complete System |
Testing |
Annually |
Full Automatic & Manual Operational Test |
§11.3.3 |
Concentrate Sample |
Testing |
Annually |
During Annual Test refractometric check |
§11.3.6 |
Maintenance |
Annually |
During Annual Test, submit sample per mfr |
§11.2.10 | |
Pump |
Maintenance |
Monthly |
Pump run, circulate foam, maintenance/mfr |
§11.4.6 & 11.4.7 |
Foam Water Sprinkler Proportioning System |
||||
Standard Pressure |
Inspection |
*Monthly |
No corrosion, ball drip valves free/opened |
§11.2.9.5.1 |
Maintenance |
Every 5 Yrs |
Disassemble/clean/reassemble ball drip valves |
§11.4.3A | |
Maintenance |
Every 10 Yr |
Drain/flush tank, hydro test |
§11.4.3BC | |
Bladder Tank |
Inspection |
*Monthly |
No corrosion, water control valves in position |
§11.2.9.5.2 |
Maintenance |
Every 10 Yr |
Remove/clean sight glass, hydro test |
§11.4.4 | |
Line Proportioner |
Inspection |
*Monthly |
No corrosion, pressure vacuum vent operable |
§11.2.9.5.3 |
Maintenance |
Every 10 Yr |
Drain/flush tank, tank/piping corrosion check |
§11.4.5 | |
Standard Balanced |
Inspection |
*Monthly |
Pressure vacuum vent, sensing lines, gauges |
§11.2.9.5.4 |
Maintenance |
Every 5 Yrs |
Flush valves, pump/drive train/driver per mfr |
§11.4.6 | |
In-Line Balanced |
Inspection |
*Monthly |
Pressure vacuum vent, sensing lines, gauges |
§11.2.9.5.5 |
Maintenance |
Every 5 Yrs |
Flush valves, pump/drive train/driver per mfr |
§11.4.7BC | |
Maintenance |
Every 10 Yr |
Internally inspect tank for corrosion |
§11.4.7.D | |
Orifice Plate |
Inspection |
*Monthly |
Pressure vacuum vent, sensing lines, gauges |
§11.2.9.5.6 |
Water Spray Fixed System |
||||
Fittings/Piping |
Inspection |
*Monthly |
No damage/corrosion/rust/missing parts |
§10.2.1&10.2.4 |
Hangers/Support |
Inspection |
*Monthly |
No damage/corrosion/rust/missing parts |
§10.2.4.2 |
Heat/Valve Room |
Inspection |
*Monthly |
Maintain 40 degrees F |
§10.2.1.5 |
Nozzles |
Inspection |
*Monthly |
No damage/corrosion, in place w/proper aim |
§10.2.1/10.2.5 |
Strainers |
Inspection |
*Per Mfr |
Flushed clear after each operation or test |
§10.2.7 |
Operational Test |
Testing |
Annually |
Full Manual & Automatic Operational Test |
§T 10.1 |
Water Storage Tanks |
||||
Water Level |
Inspection |
*Quarterly |
Where a water level alarm is provided |
§9.2.1 |
Level Alarm |
Testing |
*2Times/Year |
High and Low water level alarms tested |
§9.33.5 |
Level Indicators |
Testing |
Every 5 Years |
Accuracy and freedom of movement |
§9.3.1 |
Thermostats |
Testing |
Frequency per manufacturer’s specifications |
§9.3.2 | |
Low Temp Alarm |
Testing |
*Monthly |
Where provided, test in cold weather |
§9.3.3 |
Air Pressure |
Inspection |
*Monthly |
In pressure tanks |
§9.2.2 |
Tank Exterior |
Inspection |
*Quarterly |
Free of damage, no leakage, sound structure |
§9.2.5.1 |
Tank Support |
Maintenance |
*Per Mfr |
Embankment Supported Rubberized Fabric |
§9.4.6 |
Expansion Joints |
Inspection |
*Annually |
Where provided, no leaks, no cracks |
§9.2.5.3 |
Interior |
Inspection |
Every 5 Years Every 3 Years |
Free of damage Pressure tanks, & steel tanks w/out corrosion protection |
§9.2.6.1.1 §9.2.6.1.2 |
Sediment, Drain |
Maintenance |
*2 Times/Year |
Drain and/or flush tank |
§9.4.5 |
Cathode Protection |
Maintenance |
Annually |
Where provided, per manufacturer |
|
Drain Valves |
Maintenance |
Annually |
Cycled fully open and closed |
|
Vent Screens |
Maintenance |
Annually |
Clean |
Inspection: A visual examination to verify an item is in operating condition and free of physical damage.
Testing: A procedure used to determine the status of a system operating as intended by conducting physical checks.
Maintenance: Work performed to keep equipment operable or to make repairs.
*Servicing may be performed by an owner, but must be performed at least annually by a licensed company.
Appendix F - Table Three
Owner Performed
Testing, Inspection, and Maintenance of Fire Alarm Signaling Systems
as Required by Regulation 703, Chapter 1 and the National Fire Alarm Code, NFPA 72, 2007 Edition
This brief summary of periodic tests, inspections, and maintenance is not all inclusive, and, to assist in the performance of these services, the user is advised to purchase the applicable documents from NFPA (1-800-344-3555). These periodic tests, inspections, and maintenance may be performed by the owner or the owner’s maintenance staff. A log book must be maintained by the owner for each system. The log book must include the date the service was performed, the type of service performed, and the person performing the service. An asterisk (*) denotes servicing which must be performed at least annually (once a year) by a company licensed by the Office of State Fire Marshal, Licensing Division, (302) 739-4394.
Item |
Activity |
Frequency |
Service |
Section #/Table |
Control Equipment |
||||
Fire Alarm Systems Unmonitored for Alarm Supervisory, Trouble Signals |
||||
Fuses |
Inspection |
*Weekly |
No damage or missing parts |
Table 10.3.1 |
Interfaced Equip Inspection |
Inspection |
*Weekly |
Wiring connections secure/No damage |
Table 10.3.1 |
Lamps and LEDs Inspection |
Inspection |
*Weekly |
All lamps and LEDs illuminated |
Table 10.3.1 |
Primary (Main) Power Supply |
Inspection |
*Weekly |
Secured/Marked/No damage |
Table 10.3.1 |
Batteries |
||||
Lead-Acid |
Inspection |
*Monthly |
Electrolyte level/connections, No corrosion |
Table 10.3.1 |
Nickel-Cadmium |
Inspection |
*2 Times/Year |
No corrosion/leakage, Connections tight |
Table 10.3.1 |
Primary (Dry Cell) |
Inspection |
*Monthly |
No corrosion/leakage, Connections tight |
Table 10.3.1 |
Sealed Lead-Acid |
Inspection |
*2 Times/Year |
No corrosion/leakage, Connections tight |
Table 10.3.1 |
Transient Suppressors |
||||
Lightning Protection Equipment |
||||
Inspection |
*2 Times/Year |
Per mfr/After every lightning strikes/storms |
Table 10.3.1 and NFPA 780 | |
Remote Annunciators |
||||
Inspection |
*2 Times/Year |
Secured/No damage or missing parts |
Table 10.3.1 | |
Initiating Devices | ||||
Air Sampling |
Inspection |
*2 Times/Year |
Secured/No damage or missing parts |
Table 10.3.1 |
Duct Detectors |
Inspection |
*2 Times/Year |
Secured/No damage or missing parts |
Table 10.3.1 |
Electromechanical Releasing Device |
||||
Inspection |
*2 Times/Year |
Secured/No damage or missing parts |
Table 10.3.1 | |
Suppression System Switches |
Inspection |
*2 Times/Year |
Secured/No damage or missing parts |
Table 10.3.1 |
Fire Alarm Boxes |
Inspection |
*2 Times/Year |
Secured/No damage or missing parts |
Table 10.3.1 |
Heat Detectors |
Inspection |
*2 Times/Year |
Secured/No damage or missing parts |
Table 10.3.1 |
Radiant Energy Fire Detectors |
||||
Inspection |
*Quarterly |
No damage/obstructions/proper position |
Table 10.3.1 | |
Smoke Detectors |
Inspection |
*2 Times/Year |
Secured/No damage or missing parts |
Table 10.3.1 |
Supervisory Signal Devices |
||||
Inspection |
*Quarterly |
Secured/No damage or missing parts |
Table 10.3.1 | |
Waterflow Devices |
||||
Inspection |
*Quarterly |
Secured/No damage or missing parts |
Table 10.3.1 | |
Guard’s Tour Equipment |
||||
Inspection |
*2 Times/Year |
No damage or missing parts/equipment |
Table 10.3.1 | |
Interface Equipment |
||||
Inspection |
*2 Times/Year |
No damage or missing parts/equipment |
Table 10.3.1 | |
Alarm Notification Appliances |
||||
Audible Devices |
Inspection |
*2 Times/Year |
No damage or missing parts/equipment |
Table 10.3.1 |
Speakers |
Inspection |
*2 Times/Year |
No damage or missing parts/equipment |
Table 10.3.1 |
Visible Devices |
Inspection |
*2 Times/Year |
No damage or missing parts/equipment |
Table 10.3.1 |
Supervising Station Fire Alarm Systems - Transmitters |
||||
DACT |
Inspection |
2 Times/Year |
Secured/No damage or missing parts |
Table 10.3.1 |
DART |
Inspection |
2 Times/Year |
Secured/No damage or missing parts |
Table 10.3.1 |
McCulloh |
Inspection |
2 Times/Year |
Secured/No damage or missing parts |
Table 10.3.1 |
RAT |
Inspection |
2 Times/Year |
Secured/No damage or missing parts |
Table 10.3.1 |
Supervising Station Fire Alarm Systems - Receivers |
||||
DACR |
Inspection |
*Monthly |
Secured/No damage or missing parts |
Table 10.3.1 |
DARR |
Inspection |
2 Times/Year |
Secured/No damage or missing parts |
Table 10.3.1 |
McCulloh |
Inspection |
2 Times/Year |
Secured/No damage or missing parts |
Table 10.3.1 |
Two-Way RF Multiplex |
||||
Inspection |
2 Times/Year |
Secured/No damage or missing parts |
Table 10.3.1 | |
RASSR |
Inspection |
2 Times/Year |
Secured/No damage or missing parts |
Table 10.3.1 |
RARS |
Inspection |
2 Times/Year |
Secured/No damage or missing parts |
Table 10.3.1 |
Private Microwave Inspection |
||||
Inspection |
2 Times/Year |
Secured/No damage or missing parts |
Table 10.3.1 | |
Engine-Driven Generator |
||||
Inspection |
*Weekly |
No damage or leakage |
Table 10.3.1 | |
Testing |
*Weekly |
Verify operation |
NFPA 110 | |
Uninterrupted Power Supply (UPS) |
||||
Testing |
*Per manufacturer and NFPA 111 |
Table 10.4.4 |
Inspection: A visual examination to verify an item is in operating condition and free of physical damage.
Testing: A procedure used to determine the status of a system operating as intended by conducting physical checks.
Maintenance: Work performed to keep equipment operable or to make repairs.
*Servicing may be performed by an owner, but must be performed at least annually by a licensed company.
Appendix F - Table Four
Licensed Company Required
Testing, Inspection, and Maintenance of Fire Alarm Signaling Systems
as Required by Regulation 703, Chapter 1 and the National Fire Alarm Code, NFPA 72, 2007 Edition
This brief summary of periodic tests, inspections, and maintenance is not all inclusive, and, to assist in the performance of these services, the user is advised to purchase the applicable documents from NFPA (1-800-344-3555). These periodic services must be performed by a company licensed by the Office of State Fire Marshal, Licensing Division, (302) 739-4394. A log book must be maintained by the licensed company for each system. The log book must include the date the service was performed, the type of service performed, and the person performing the service. An asterisk (*) denotes servicing which may be performed by an owner, but must be performed at least annually (once a year) by a licensed company. A licensed company must forward a Certificate of Inspection to the Office of State Fire Marshal within 30 days of the annual inspection.
Item |
Activity |
Frequency |
Service |
Section #/Table |
Control Equipment |
||||
Fire Alarm Systems Unmonitored for Alarm Supervisory, Trouble Signals | ||||
Fuses |
Inspection |
*Weekly |
No damage or missing parts |
Table 10.3.1 |
Testing |
Quarterly |
Remove fuse & verify rating & supervision |
Table 10.4.4 | |
Interfaced Equip |
Inspection |
*Weekly |
Wiring connections secure/No damage |
Table 10.3.1 |
Testing |
Quarterly |
Verify integrity & signals by operational test |
Table 10.4.4 | |
Lamps & LEDs |
*Weekly |
*Weekly |
All lamps and LEDs illuminated |
Table 10.3.1 |
Quarterly |
Quarterly |
All lamps and LEDs illuminated |
Table 10.4.4 | |
Primary (Main) Power Supply |
Inspection |
*Weekly |
Secured/Marked/No damage |
Table 10.3.1 |
Testing |
Quarterly |
Disconnect secondary power, max load test |
Table 10.4.4 | |
Functions |
Testing |
Quarterly |
Full Function Test |
Table 10.4.4 |
Transponders |
Testing |
Quarterly |
Full Function Test |
Table 10.4.4 |
Fire Alarm Systems Monitored for Alarm Supervisory, Trouble Signals |
||||
Fuses |
Inspection |
*Weekly |
No damage or missing parts |
Table 10.3.1 |
Testing |
Quarterly |
Remove fuse & verify rating & supervision |
Table 10.4.4 | |
Interfaced Equip |
Inspection |
Annually |
No damage or missing parts |
Table 10.3.1 |
Testing |
Annually |
Verify integrity & signals by operational test |
Table 10.4.4 | |
Lamps & LEDs |
Inspection |
Annually |
No damage or missing parts |
Table 10.3.1 |
Testing |
Annually |
All lamps and LEDs illuminated |
Table 10.4.4 | |
Primary (Main) Power Supply |
Inspection |
Annually |
No damage or missing parts |
Table 10.3.1 |
Testing |
Annually |
Disconnect secondary power, max load test |
Table 10.4.4 | |
Functions |
Testing |
Annually |
Full Function Test |
Table 10.4.4 |
Transponders |
Testing |
Annually |
Full Function Test |
Table 10.4.4 |
Batteries |
||||
Lead-Acid |
Inspection |
*Monthly |
Electrolyte level/connections, No corrosion |
Table 10.3.1 |
Testing |
2 Times/Year |
Discharge, Load Voltage, Specific Gravity |
Table 10.4.4 | |
Testing |
Annually |
Charger Test |
Table 10.4.4 | |
Nickel-Cadmium |
Inspection |
2 Times/Year |
No corrosion/leakage, Connections tight |
Table 10.3.1 |
Testing |
2 Times/Year |
Load Voltage |
Table 10.4.4 | |
Testing |
Annually |
Charger Test, Discharge (30 min) Test |
Table 10.4.4 | |
Primary (Dry Cell) |
Inspection |
*Monthly |
No corrosion/leakage, Connections tight |
Table 10.3.1 |
Testing |
Monthly |
Load Voltage |
Table 10.4.4 | |
Sealed Lead-Acid |
Inspection |
*2 Times/Year |
No corrosion/leakage, Connections tight |
Table 10.3.1 |
Testing |
2 Times/Year |
Load Voltage |
Table 10.4.4 | |
Testing |
Annually |
Charger Test, Discharge (30 min) Test |
Table 10.4.4 | |
Transient Suppressors |
||||
Lightning Protection Equipment |
||||
Inspection |
*2 Times/Year |
Per mfr/After every lightning strikes/storms |
Table 10.3.1 & NFPA 780 | |
Testing |
Per mfr and NFPA 780 | |||
Remote Annunciators |
||||
Inspection |
*2 Times/Year |
Secured/No damage or missing parts |
Table 10.3.1 | |
Testing |
Annual |
Verify operation & identification |
Table 10.4.4 | |
Initiating Devices | ||||
Air Sampling |
Inspection |
*2 Times/Year |
Secured/No damage or missing parts |
Table 10.3.1 |
Testing |
Annually |
Verify alarm & airflow via ports per mfr |
Table 10.4.4 | |
Duct Detectors |
Inspection |
*2 Times/Year |
Secured/No damage or missing parts |
Table 10.3.1 |
Testing |
Annually |
Verify per manufacturer |
Table 10.4.4 | |
Electromechanical Releasing Device |
||||
Inspection |
*2 Times/Year |
Secured/No damage or missing parts |
Table 10.3.1 | |
Nonrestorable |
Testing |
Annually |
Remove link, ensure operation, lubricate |
Table 10.4.4 |
Restorable |
Testing |
Annually |
Remove link, ensure operation, lubricate |
Table 10.4.4 |
Suppression System Switches |
||||
Inspection |
*2 Times/Year |
Secured/No damage or missing parts |
Table 10.3.1 | |
Testing |
Annually |
Mechanical/electrical operation of switch Verify signal receipt at panel |
Table 10.4.4 | |
Fire Alarm Boxes |
Inspection |
*2 Times/Year |
Secured/No damage or missing parts |
Table 10.3.1 |
Testing |
Annually |
Operate per manufacturer |
Table 10.4.4 | |
Heat Detectors/All |
Inspection |
*2 Times/Year |
Secured/No damage or missing parts |
Table 10.3.1 |
Fixed-Temp |
Testing |
Annually |
Heat test per manufacturer |
Table 10.4.4 |
Rate-of-Rise, Rate-of-Compensation, Restorable Line, Spot Type (excluding Pneumatic Tub Type) Fixed-Temp | ||||
Testing |
Annually |
Mechanical/electrical tests/Loop resistance |
Table 10.4.4 | |
Nonrestorable Line Type Fixed-Temp. |
||||
Testing |
After 15 Years |
Replace all devices or Lab test 2 per 100 |
Table 10.4.4 | |
Nonrestorable Spot Type |
||||
Testing |
Annually |
Mechanical/electrical function tests |
Table 10.4.4 | |
(General) Restorable Line |
||||
Testing |
Annually |
Heat source or pressure pump |
Table 10.4.4 | |
Radiant Energy Fire Detectors |
||||
Inspection |
*Quarterly |
No damage/obstructions/proper position |
Table 10.3.1 | |
Testing |
2 Times/Year |
Per manufacturer and Sensitivity Tests |
Table 10.4.4 | |
Smoke Detectors |
Inspection |
*2 Times/Year |
Secured/No damage or missing parts |
Table 10.3.1 |
Testing |
Annually |
Functional Test |
Table 10.4.4 | |
Testing |
1st Year and Alternating Yrs Sensitivity Test |
(IF within listed and marked sensitivity range) |
Table 10.4.4 | |
Supervisory Signal Devices |
||||
Inspection |
*Quarterly |
Secured/No damage or missing parts |
Table 10.3.1 | |
Control Valve |
Testing |
Quarterly |
Operate valve per mfr/Verify signal receipt |
Table 10.4.4 |
High-/Low-Air |
Testing |
Quarterly |
Operate valve per mfr/Verify signal receipt |
Table 10.4.4 |
Room Temp |
Testing |
Quarterly |
Operate switch/Verify signal receipt |
Table 10.4.4 |
Water Level |
Testing |
Quarterly |
Operate switch/Verify signal receipt |
Table 10.4.4 |
Water Temp |
Testing |
Quarterly |
Operate switch/Verify signal receipt |
Table 10.4.4 |
Water Flow |
Testing |
Quarterly |
Flow water per NFPA 25 |
Table 10.4.4 |
Valve Tamper Sw |
Testing |
2 Times/Year |
Operate switch per mfr/Verify signal receipt |
Table 10.4.4 |
Waterflow Devices |
||||
Inspection |
*Quarterly |
Secured/No damage or missing parts |
Table 10.3.1 | |
Testing |
2 Times/Year |
Operate switch per mfr/Verify signal receipt |
Table 10.4.4 | |
Fire-Gas & Other |
Testing |
Annually |
Per manufacturer |
Table 10.4.4 |
Guard’s Tour Equipment |
||||
Inspection |
*2 Times/Year |
No damage or missing parts/equipment |
Table 10.3.1 | |
Testing |
Annual |
Per manufacturer |
Table 10.4.4 | |
Interface Equipment |
||||
Inspection |
*2 Times/Year |
Secured/No damage or missing parts |
Table 10.3.1 | |
Testing |
Annual |
Operational test/Verify signal receipt |
Table 10.4.4 | |
Alarm Notification Appliances |
||||
Audible Devices |
Inspection |
*2 Times/Year |
Secured/No damage or missing parts |
Table 10.3.1 |
Testing |
Annual |
Measure sound level IAW ANSI S-1.4a |
Table 10.4.4 | |
Speakers |
Inspection |
*2 Times/Year |
Secured/No damage or missing parts |
Table 10.3.1 |
Testing |
Annual |
Measure sound level IAW ANSI S-1.4a Verify Voice Clarity |
Table 10.4.4 | |
Visible Devices |
Inspection |
*2 Times/Year |
Secured/No damage or missing parts |
Table 10.3.1 |
Testing |
Annual |
Per manufacturer |
Table 10.4.4 | |
Supervising Station Fire Alarm Systems - Transmitters |
||||
All Equipment |
Testing |
Annual |
Per mfr/operational test/verify signal receipt |
Table 10.4.4 |
DACT |
Inspection |
*2 Times/Year |
Secured/No damage or missing parts |
Table 10.3.1 |
Testing |
Annual |
2 lines/line seizure/trouble signal w/in 90 sec |
Table 10.4.4 | |
DART |
Inspection |
*2 Times/Year |
Secured/No damage or missing parts |
Table 10.3.1 |
Testing |
Annual |
3 rounds-3 impulses/end-end metallic/etc |
Table 10.4.4 | |
McCulloh |
Inspection |
*2 Times/Year |
Secured/No damage or missing parts |
Table 10.3.1 |
Testing |
Annual |
2 lines/line seizure/trouble signal w/in 90 sec |
Table 10.4.4 | |
RAT |
Inspection |
*2 Times/Year |
Secured/No damage or missing parts |
Table 10.3.1 |
Testing |
Annual |
Fault indication/trouble signal |
Table 10.4.4 | |
Supervising Station Fire Alarm Systems - Receivers | ||||
All Equipment |
Testing |
Monthly |
Per mfr/operational test/verify signal receipt |
Table 10.4.4 |
DACR |
Inspection |
*Monthly |
Secured/No damage or missing parts |
Table 10.3.1 |
Testing |
Annual |
Trouble signal/verify 24-hour signals |
Table 10.4.4 | |
DARR |
Inspection |
*2 Times/Year |
Secured/No damage or missing parts |
Table 10.3.1 |
Testing |
Monthly |
Verify signals for all 4 trouble conditions/etc |
Table 10.4.4 | |
McCulloh |
Inspection |
*2 Times/Year |
Secured/No damage or missing parts |
Table 10.3.1 |
Testing |
Annual |
2 lines/line seizure/trouble signal w/in 90 sec |
Table 10.4.4 | |
Two-Way RF Multiplex |
||||
Inspection |
*2 Times/Year |
Secured/No damage or missing parts |
Table 10.3.1 | |
Testing |
Monthly |
Per mfr/operational test/verify signal receipt |
Table 10.4.4 | |
RASSR & RARSR |
Inspection |
*2 Times/Year |
Secured/No damage or missing parts |
Table 10.3.1 |
Testing |
Monthly |
Verify signals for all 3 trouble conditions |
Table 10.4.4 | |
Private Microwave |
||||
Inspection |
*2 Times/Year |
Secured/No damage or missing parts |
Table 10.3.1 | |
Testing |
Monthly |
Verify signals for all 4 trouble conditions/etc |
Table 10.4.4 | |
Engine-Driven Generator |
||||
Inspection |
*Weekly |
No damage or leakage |
Table 10.3.1 | |
Testing |
*Weekly |
Verify operation |
NFPA 110 | |
Uninterrupted Power Supply (UPS) |
||||
Testing |
*Per manufacturer and NFPA 111 |
Table 10.4.4 | ||
Secondary (Standby) Power Supply |
||||
Testing |
Annually |
Disconnect primary/verify trouble signal/etc |
Table 10.4.4 | |
Control Panel Trouble Signals |
||||
Testing |
Annually |
Audible/Visible, Disconnect Switches, Ground-Faults, Signal Transmission Off-Site |
Table 10.4.4 | |
Conductors |
||||
Metallic |
Testing |
Annually |
Stray Voltage, Short Circuit Faults, Ground Faults, Loop Resistance |
Table 10.4.4 |
Nonmetallic Fiber Optics/Fiber Optics Cable Power |
||||
Testing |
Annually |
Circuit Integrity, Supervision |
Table 10.4.4 | |
Emergency Voice/Alarm Communications Equipment |
||||
Inspection |
Annually |
No damage or missing parts |
Table 10.3.1 | |
Phone Set, Phone Jacks, Amplifier/Tone Generators, Call-In Signal Silence, Off-Hook Indicator (Ring Down), System Performance |
||||
Testing |
Annually |
Full Function Test |
Table 10.4.4 | |
Special Hazard Equipment |
||||
Abort Switches, Cross-Zone Detection Circuits Matrix-Type Circuit, Release Solenoid, Squibb Release Circuit, Verified/Sequential/Counting Zone Circuit, All other devices or circuits or combinations thereof. | ||||
Testing |
Annually |
Operate switches/sensors and verify |
Table 10.4.4 | |
Special Procedures |
||||
Inspection |
2 Times/Year |
No damage or missing parts |
Table 10.3.1 | |
Testing |
Annually |
Alarm Verification/Multiplex Systems |
Table 10.4.4 | |
Low Power Radio (Wireless Systems) |
||||
Testing |
Monthly |
Per manufacturer |
Table10.4.4 |
Inspection: A visual examination to verify an item is in operating condition and free of physical damage.
Testing: A procedure used to determine the status of a system operating as intended by conducting physical checks.
Maintenance: Work performed to keep equipment operable or to make repairs.
*Servicing may be performed by an owner, but must be performed at least annually by a licensed company